Brand Name: | OEM |
Model Number: | JM-X-7 |
MOQ: | 1 set |
Payment Terms: | T/T |
Supply Ability: | 1000sets |
Use
This transmitter is used to turn travel values of various rotating machinery(such as: oil engine, thermal expansion, power limiter, synchronizer, activated valve, oil.level), to standard 4~20mA, which can be fed to PLC, DCS and DEHsystems.
Functions
1.Applying to measuring diaplancement of oil engine, themal expansion, power limiter, synchronizer, activated value,oil level, etc,in rotating mechanisms.
2.Suitable for on-line monitoring for a long time, easy to installand debug, needing no site maintenance.
3.4~20mA analog current output.
Technical parameters
1.Measuring range:
JM-X-71 oil engline transmitter measuringrange:0~150mm,0~200mm,0~150mm
JM-X-72 thermal expansion transmitter measuring range:0~35.0mm
JM-X-73 valve status transmitter measuring range:0~25.0mm
JM-X-74 oil level transmitter measuring rrange:-200~200mm
2.Measuring accuracy:±0.5 class, linear error≤1%FS
3.Input signals: TD-1 oil engline sensor, TD-2 thermal expansion sensor;
TDZ-1 power limiter, synchronizer, activated value sensor;
UT-81 oil level sensor;
4.Output signal: Current output: 4~20mA(load≤1KΩ)
5.Environment temperature: -10~80℃
relative humidity≤85%(sensor)
temperature:-10~45℃
relative humidity≤80%(transmitter)
6.Power voltage: DC +24(power consumed≤3W)
7.External dimension: 120mm(length)×90mm(width)×55mm(height)
8. Installation hole size and pattern: 90(length)×80mm(wigth)(diameter: Φ5.2mm)