| Brand Name: | ABB |
| Model Number: | AI893 |
| MOQ: | 1 |
| Price: | Negotiations |
| U0 (Groups CENELEC USA) | IIC | I0 (Groups CENELEC USA) | IIB | P0 (Groups CENELEC USA) | IIA |
|---|---|---|
| U0 - C0 (uF) | 1.41 | I0 - C0 (uF) | 9 | P0 - C0 (uF) | 36 |
| U0 -L0 (mH) | 88 | I0 -L0 (mH) | 352 | P0 -L0 (mH) | 706 |
| U0 -L/R (uH/O) | 586 | I0 -L/R (uH/O) | 2347 | P0 -L/R (uH/O) | 4707 |
| CE mark | Yes |
|---|---|
| Electrical safety | IEC 61131-2, FM |
| Hazardous Location | C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2 |
| Marine certification | - |
| Protection rating | IP20 according to IEC 60529 |
| Corrosive atmosphere ISA-S71.04 | G3 |
| Climatic operating conditions | 0 to +55 °C (Storage -40 to +70 °C), RH=5 to 95 % no condensation, IEC/EN 61131-2 |
| Pollution degree | Degree 2, IEC 60664-1 |
| Mechanical operating conditions | IEC/EN 61131-2 |
| EMC | EN 61000-6-4, EN 61000-6-2 |
| Overvoltage categories | IEC/EN 60664-1, EN 50178 |
| Equipment class | Class I according to IEC 61140; (earth protected) |
| Max ambient temperature | 55 °C (131 °F), for vertical mounting in compact MTU 40 °C (104 °F) |
| RoHS compliance | EN 50581:2012 |
| WEEE compliance | DIRECTIVE/2012/19/EU |
| Resolution | 15 bit + sign |
|---|---|
| Input impedance | >10 MΩ |
| Isolation | Groupwise isolated from ground |
| Error | TC/mV: <20 µV ; RTD (0-400 Ω): <0.1 Ω ; RTD (0-4000 Ω): <1 Ω |
| Temperature drift | TC/mV: <20 µV/10°C ; RTD (0-400 Ω): <0.1 Ω/10°C ; RTD (0-4000 Ω): <1 Ω/10°C |
| Update cycle time | (no of active channels) x 125 + 125 ms |
| Common mode voltage input | +/- 5V |
| CMRR, 50Hz, 60Hz | >100 dB |
| NMRR, 50Hz, 60Hz | >80 dB |
| Rated insulation voltage | 50V |
| Dielectric test voltage | 500 V a.c. |
| Power dissipation | 0.5 W |
| Current consumption +5 V Modulebus | Typ. 90 mA, Max. <125 mA |