| Brand Name: | Schneider |
| Model Number: | 140AVI03000 |
| MOQ: | 1 |
| Price: | Negotiations |
| Manufacturer | Schneider Electric |
|---|---|
| Series | Modicon Quantum |
| Module format | Standard |
| Type of filter | Single pole low pass - 3 dB at 847 Hz +/- 20 % |
| Analogue input number | 8 |
| Input type | Differential |
| Addressing requirement | 9 input words |
| Analogue input type | Unipolar voltage 0...5 V Unipolar voltage 0...10 V Unipolar current 0...20 mA Bipolar voltage +/- 5 V Bipolar voltage +/- 10 V Bipolar current 20 mA |
| Analogue input resolution | 16 bits 20 mA 16 bits 0...5 V 16 bits 0...20 mA 16 bits 0...10 V 16 bits +/- 5 V 16 bits +/- 10 V |
| Linear measuring range | (Input range) x 1.024 mA (Input range) x 1.024 V |
| Absolute maximum input | 50 V DC 25 mA |
| Input impedance | 250 MOhm +/- 0.03 % > 20 Ohm voltage |
| Absolute accuracy error | +/- 0.05 % of full scale maximum +/- 0.03 % |
| Linearity error | +/- 0.008 % |
| Accuracy drift according to temperature | <= 0.004 % of full scale /°C +/- 0.0015 % of full scale/°C |
| Common mode rejection | > -80 dB 60 Hz |
| Isolation between channels and bus | 750 V DC 500 Vrms AC for 60 s |
| Isolation between channels | 135 Vrms AC 200 V DC |
| Update time | 10 ms |
| Fault type | Overtacking scale 1...5 V Broken wire 4...20 mA |
| Marking | CE |
| Local signalling | 8 LEDs red channel fault 8 LEDs green channel is turned on 1 LED red external fault 1 LED green bus communication is present (Active) |
| Bus current requirement | 280 mA |
| Power dissipation in W | 2.2 W |